HRX-OM-R026
Chapter 9 Documents
9.1
Specifications
HRSH Series
9-2
9.1.2
HRSH090-A
-40-
Table 9-2 Specifications [HRSH090-A
-40-
]
Model
HRSH090-A
-40-
Cooling method
Air-cooled refrigerated type
Refrigerant
R410A (HFC) (GWP1975)
Control method
PIDcontrol
Ambient temperature
1
o
C
5 to 45
Circulating
fluid
system
Circulating fluid
2
Tap water, Ethylene glycol aqueous solution 15%
Operating temperature range
1
o
C
5 to 40
Cooling capacity
3
kW
9.5
Heating capacity
4
kW
2.5
Temperature stability
5
o
C
±0.1
Pump
capacity
Rated
flow
rate
(Outlet)
L/min
45 (0.5MPa)
Maximum flow rate
L/min
60
Maximum
lifting
height
m
50
Settable pressure range
6
MPa
0.1 to 0.5
Minimum operating flow rate
7
L/min
20
Tank capacity
L
18
Circulating fluid outlet, circulating fluid
return port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Tank drain port
Rc1/4 (Symbol F: G1/4, Symbol N: NPT1/4)
Wetted material
10
Stainless, Copper(
Heat exchanger’s brazing ), Bronze, Brass, Carbon,
Ceramic, PE, PVC, POM, PTFE, NBR, EPDM, FKM, PP
Electric
system
Power supply
AC380-415V 50/60Hz 3phase
Allowable voltage fluctuation ±10% (No continuous voltage fluctuation)
AC460-480V 60Hz
3-phase
Allowable voltage fluct4%,
–10%
(Max. voltage less than 500 V and no continuous voltage fluctuation)
Recommended
earth
leakage
breaker
8
Rated
current
A
20
Sensitivity
mA
30
Rated operating current
5
A
8
Rated
power
consumption
5
kW (kVA)
5.0 (5.6)
Sound level (F
ront 1m / Height 1m)
5
dB(A)
66
Accessory
Alarm cord list label 2pc.(English 1pc./Japanese 1pc.), Operation manual
2pc. (English 1pc./Japanese 1pc.),
Y strainer (40 meshes) 25A, Barrel nipple 25A
Anchor brackets 2pcs.(including M10 bolts 4pcs.)
9
Weight
(dry condition)
kg
Approx.130
1 Use 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. or ambient temperature is lower than
10
o
C
2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: diluted by tap water in condition above without any additives such as antiseptics.
Deionized wate: Conductivity 1
μS/cm and higher (electrical resistivity 1MΩ
・
cm and lower)
3 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Criculating fluid flow rate : Rated
flow rate, (5)Power supply: AC400V
4 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Criculating fluid flow rate : Rated flow rate, (4)Power supply:
AC400V
5 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Heat load : Same as the cooling
capacity, (5)Circulating fluid flow rate: Rated flow rate, (6)Power : AC400V, (7) External piping length: Minimum.
6
With the pressure control mode of the pump operation mode. When the pressure control mode is not necessary, use the frequency set
mode
7
Fluid flow rate to maintain the cooling capacity. If the actual flow rate is lower than this, please install a bypass piping.
8
A specified earth leakage breaker is installed for HRSH090-A
-40-
.
9
The anchor brackets (including M10 bolts) are used for fixation with the skid when this product is packed. The anchor bolts are not
attached.
10
Copper, bronze and brass is not included when option M [ DI water (pure water) piping]
is selected.
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......