HRX-OM-R026
Chapter 3 Transport and Setting Up
3.4
Piping
HRSH Series
3-26
3.4 Piping
Piping port size
Table 3-12 Piping port size
Name
Port size
Recommended
tightening torque
Recommended piping
specification
Circulating fluid supply
Rc1
36 to 38N
・
m
1.0MPa and more
Circulating fluid return
Rc1
36 to 38N
・
m
1.0MPa and more
Drain port
Rc1/4
8 to 12N
・
m
-
Facility water inlet *
1
Rc1/2
28 to 30N
・
m
1.0MPa and more.
(Supply puressure : 0.3 to
0.5MPa)
Facility water outlet *
1
Rc1/2
28 to 30N
・
m
Automatic water-fill port
Rc3/8
22 to 24N
・
m
1.0MPa more
(
Automatic water-fill pressure
0.2 to 0.5MPa
)
Overflow port
Rc3/4
28 to 30N
・
m
Inside diameter 19mm more of
piping
*1 : Water cooled type only.
*2 : For Option J [Automatic fluid filling]
【
Tips
】
<In case of HRSH
-AN-
-
、
HRSH
-WN-
-
>
A set of thread adapters that converts the connections from Rc to NPT is
enclosed as an accessory. Be sure to use this for NPT piping.
<In case of HRSH
-AF-
-
、
HRSH
-WF-
-
>
A set of thread adapters that converts the connections from Rc to G is
enclosed as an accessory. Be sure to use this for G piping.
Connect piping firmly. Incorrect piping might cause leakage of
supplied or drained leakage and wet surrounding area and facility.
Pay attention not to allow dust and foreign materials to enter into
water circuit etc. during connection of piping.
During piping work, residual liquid may drip from the circulating
fluid circuit or facility water circuit. Prepare a drain pan near the
pipe connection so that the residual liquid can be received.
Hold the piping port firmly with specific wrench when tightening.
The piping should be selected with due consideraton of pressure
and temperature. Otherwise the piping can burst in service.
Use non-corrosive material for fluid contact parts of circulating
fluid and/or facility water. Also, the use of corrosive materials
such as aluminum or iron for fluid contact parts, such as piping,
may not only lead to clogging or leakage in the circulating fluid
and facility water circuits but also refrigerant leakage and other
unexpected problems. Provide protection against corrosion when
you use the product.
Do not generate a rapid change of pressure by water hammer etc.
The product and external piping might be damaged.
Facility water temperature of the facility water outlet port might
rise up to approx.60deg.C.
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......