HRX-OM-R026
Chapter 5 Display and setting of various functions
5.8
Ready completion (TEMP READY) signal
HRSH Series
5-22
5.
Select READY band width (upper/lower temperature range) from the table below with
[
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.8-3
List of set value
Set value
Explanation
Initial
(Default setting)
Setting and checking are not available when
READY mode setting is OFF.
Centigrade
to
Set
READY
band
width
(upper/lower
temperature range) for the circulating fluid
temperature
Temperature unit is Centigrade : Setting unit is
0.1
o
C
Temperature unit is Fahrenheit : Setting unit is
0.1
o
F
Fahrenheit
to
READY time Set and checking
6.
Press the [SEL] key once.
The set screen of READY time is displayed on the digital display.
7.
Set READY time as the table below with [
▲] key or [▼] key, and confirm by pressing
“SEL”.
Table 5.8-4
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available when
READY mode setting is OFF.
to
Sets ultimate time.
Set unit is 1 sec.
8.
Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV
PV
SV
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......