HRX-OM-R026
Chapter 5 Display and setting of various functions
5.21
Communication function
HRSH Series
5-76
26.
Select responce delay time (simple communication protocol) from the table below with
[
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.21-14
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available unless the
serial
protocol
setting
is
simple
communication protocol.
to
Setting of response delay time.
Set range is 0 to 250m sec.
Communication range (simple communication protocol) Setting
and checking
27.
Press the [SEL] key once.
The set screen of communication range (simple communication protocol) is displayed
on the digital display.
28.
Select communication range (simple communication protocol) from the table below with
[
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.21-15
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available unless the
serial
protocol
setting
is
simple
communication protocol.
Only reading is available
Reading and writing are available
Contact input signal 1 Setting
and checking
29.
Press the [SEL] key once.
The set screen of contact input signal 1 is displayed on the digital display.
PV
SV
PV
SV
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......