HRX-OM-R026
Chapter 3 Transport and Setting Up
3.3
Installation
HRSH Series
3-18
Table 3-6 Power supply, contact specifications
Name
Terminal NO.
Specification
Power supply output
5, 6, 7 (DC 24V)
DC 24V ±10% 500mA MAX
1
13,14, 15 (24V COM)
Contact input signal 1
3 (Contact input signal 1)
-Run/stop
signal
input
-External
switch
signal input
2
Switch
the
input on the
operation
display panel.
Refer to the
operation
manual
communication
function.
11 (Common of contact output signal 1)
Contact input signal 2
4 (Contact input signal 2)
-Run/stop
signal
input
-Remote
signal
input
-External
switch
signal input
2
12 (Common of contact output signal 2)
1:
To use the power of the device, the total load current must be 500mA or less.
If the load is 500mA or more, the internal fuse will be cut to protect the product and the alarm [AL21 DC
line fuse cut] will be generated. Refer to Chapter 6 for handling of alarms.
2: Refer to 3.3.6 Wiring of external switch signal input.
1.
Prepare the switch (source voltage: 24V, contact capacity: 35mA or more, min. load
current: 5mA), and cable (Table 3-5 Signal cable).
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......