HRX-OM-R026
Chapter 5 Display and setting of various functions
HRSH Series
5.21
Communication function
5-79
38.
Select contact input signal 2 from the table below with [
▲] key or [▼] key, and confirm
by pressing “SEL”.
Table 5.21-20
List of set value
Set value
Explanation
Initial value
(Default setting)
Without signal input
Run/stop signal input
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Remote signal input
7
7
:
When the setting of the serial protocol is “Simplified communication protocol 2”, “Remote
signal” cannot be set.
Contact input signal 2 type Setting
and checking
39.
Press the [SEL] key once.
The set screen of contact input signal 2 type
is displayed on the digital display.
40.
Select contact input signal 2 type from the table below with [
▲] key or [▼] key, and
confirm by pressing “SEL”.
Table 5.21-21
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
Momentary signal
8
8 Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote signal"
Contact input signal 2 delay timer of reading
Setting
and checking
41.
Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading
is displayed on the
digital display.
PV
SV
PV
SV
Содержание HRSH090 Series
Страница 8: ...HRX OM R026 Contents HRSH Series...
Страница 20: ...HRX OM R026 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRSH Series 2 6...
Страница 52: ......
Страница 62: ......
Страница 126: ...HRX OM R026 Chapter 5 Display and setting of various functions 5 20 Alarm customizing function HRSH Series 5 64...
Страница 148: ......
Страница 172: ...HRX OM R026 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRSH Series 8 10...
Страница 177: ...HRX OM R026 Chapter 9 Documents HRSH Series 9 1 Specifications 9 5...
Страница 193: ......