43
command is ^S009CHMC
01.0
to ^S009CHMC
4.0
)
10.1.2 PF1.0 unit with standard LCD set charger current
Power on the unit with battery, but don’t start up the unit. Then send the command.
Noted1
: Enter the “
^S009CHMC04.0
” command and click “
Send
”. UPS will return
“
^D006ACK
” when it accept.
(
The parameter settings will be saved only when UPS
shuts down normally with battery connection.
)
Noted2:
The range of charger current is from
1A
to
12A for one charger board
.(The
command is ^S009CHMC
01.0
to ^S009CHMC
12.0
)
Noted3
: the newest 40K and 80K unit each charger board is 16A, so for 40K can set
to maximum 16A charger current and 80K can set to maximum 32A charger current.