26
displayed.
16
Inverter L3
output short
When INV phase L3
output
voltage keeps lower and
output current keeps
higher than normal, the
fault signal will be
displayed.
17
Inverter
L1L2
output short
When INV phase L1-
phase
L2(Line to line) voltage
keeps lower and output
current keeps higher than
normal, the fault signal will
be displayed
Remove all the loads. Turn off the UPS.
Check
whether the output of UPS and loads are
short
circuited. Make sure the short circuit is
removed, and the UPS has no internal faults
before turning on again.
18
Inverter
L2L3
output short
When INV phase L2-
phase
L3(Line to line) voltage
keeps lower and output
current keeps higher than
normal, the fault signal will
be displayed
19
Inverter
L3L1
output short
When INV phase L3-
phase
L1(Line to line) voltage
keeps lower and output
current keeps higher than
normal, the fault signal will
be displayed
1A
None
Inverter
L1
negative
power
fault
When the output power on
the INV phase L1 terminal
is
overpower, the fault signal
will be displayed
Remove all the loads. Turn off the UPS.
Check
whether the output of UPS and loads are
short
circuited. Make sure the short circuit is
removed, and the UPS has no internal faults
before turning on again.
1B
None
Inverter
L2
negative
power
fault
When the output power on
the INV phase L2 terminal
is
over power, the fault signal
will be displayed
1C
None
Inverter
L3
negative
power
fault
When the output power on
the INV phase L3 terminal
is
over power, the fault signal
will be displayed
23
None
Inverter relay open
The
inverter
voltage
detection is normal, but the
output voltage difference
Check the INV relay circuited
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...