56
12. 1.5 ^C0NNN<0x0d>
This command is to adjust the negative battery voltage sampling value. You can adjust the parameter to
the sampling voltage displayed on LCD and the real battery voltage. The format is:
Computer: ^C0NNN<0x0d>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Voltage adjustment step: <nnn>. n=000, 001……, 999.
For example:
Computer: ^C010BATNV-001<0x0d>
UPS: (ACK
Meanings: Battery sampling voltage will decrease about 0.1%.
12.1.6 ^P004QWS<0x0d>
^P004QWS<0x0d> means to request the current warning of the UPS. The command format is:
Computer: ^P004QWS<0x0d>
UPS: (a0a1……a62a63<cr>
a0,…,a63 is the warning status. If the warning is happened, the relevant bit will set 1, else the relevant
bit will set 0.
Bit
Warning
a0
Battery disconnected
a1
Input Neutral loss
a2
Reserved
a3
Input phase abnormal
a4
Reserved
a5
Reserved
a6
Battery over charge
a7
Low battery
a8
Overload
a9
Fan failure
a10
EPO active
a11
Reserved
a12
Over temperature
a13
Charger failure
a14
Reserved
a15
L1 IP fuse broken
a16-a49
Reserved
a50
Locked in bypass after overload 3 times in 30min
a51
Converter current unbalance
a52
Battery fuse broken
a53
Inverter inter-current unbalance
a54-a56
Reserved
a57
Cover of maintain switch is open
Example:
Computer:
^P004QWS<0x0d>
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...