54
12. Appendix
12.1 Basic communication command
In this section, we will show you some basic communication commands that will help you debug or
regulate the UPS system.
12.1.1 ^P005Q3GS<0x0d>
^P005Q3GS<0x0d> means to request general status parameters of the system. The command format is:
Computer: ^P005Q3GS<0x0d>
UPS:
^D113AA,BBB.B,CCC.C,DDD.D,EE.E,FFF.F,GGG.G,HHH.H,II.I,JJJ.J,KKK.K,LLL.L,MMM.M,NNN.N,OO
O.O,PPP.P,QQQ.Q,RRR.R,SSS,b9b8b7b6b5b4b3b2b1b0a0<CRC H><CRC L><0x0d>
Data
Description
Notes
AA
UPS Work mode
UPS Work mode
BBB.B
Line Voltage R
B is an Integer number 0 to 9. The units is V.
CCC.C
Line Voltage S
C is an Integer number 0 to 9. The units is V.
DDD.D
Line Voltage T
D is an Integer number 0 to 9. The units is V.
EE.E
Line frequency
E is an Integer number 0 to 9. The units is Hz.
FFF.F
Output Voltage R
F is an Integer number 0 to 9. The units is V.
GGG.G
Output Voltage S
G is an Integer number 0 to 9. The units is V.
HHH.H
Output Voltage T
H is an Integer number 0 to 9. The units is V.
II.I
Output Frequency
I is an Integer number 0 to 9. The units is Hz.
JJJ.J
Output Current R
J is an Integer number from 0 to 9. The units is A.
KKK.K
Output Current S
K is an Integer number from 0 to 9. The units is A.
LLL.L
Output Current T
L is an Integer number from 0 to 9. The units is A.
MMM.M
Load Percent R
M is Maximum of W% or VA%.
VA% is a percent of power.
W% is a percent of maximum active power.
NNN.N
Load Percent S
N is Maximum of W% or VA%.
VA% is a percent of power.
W% is a percent of maximum active power.
OOO.O
Load Percent T
T is Maximum of W% or VA%.
VA% is a percent of power.
W% is a percent of maximum active power.
PPP.P
Total Load Percent
P is Maximum of W% or VA%.
VA% is a percent of power.
W% is a percent of maximum active power.
QQQ.Q
Battery voltage P
Q is an Integer number 0 to 9. The units is V.
RRR.R
Battery voltage N
R is an Integer number 0 to 9. The units is V.
SSS
Max temperature
S is an integer ranging from 0 to 9. The units is °C
b9b8
Ups type (
b7
Utility Fail
b6
Battery Low
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...