42
10
How to set the parameter
10.1 How to set the charger current
10.1.1 PF0.9 unit with standard LCD set charger current
Power on the unit with battery, but don’t start up the unit. Then send the command.
Noted1
: Enter the “
^S009CHMC04.0
” command and click “
Send
”. UPS will return
“
^D006ACK
” when it accept.
(
The parameter settings will be saved only when UPS
shuts down normally with battery connection.
)
Noted2:
The range of charger current is from
1A
to
4A for one charger board
.(The
Содержание SBOL50KTIII-3