30
Model
Type
JS6
JS5
JS4
Pin1&pin2 Pin3&pin4 Pin5&pin6 Pin7&pin8
30K
0
0
1
0
0
0
30KL
0
0
1
0
1
0
60K
0
1
0
0
0
1
60KL
0
1
0
0
1
1
100KL
1
0
0
0
1
1
120KL
0
1
0
0
1
1
180KL
0
1
0
0
1
1
200KL
0
0
1
0
1
1
Note
:
“1” indicates that the jumper is connected;
“0”indicates that nothing is connected,
For long run model, The 30KL’s charge board on the INV board
(
71-304125-XXG
)。
The 30KL’s
default charging current is 4A for battery configuration.
For standard mode, The 30K’s charge board on the INV board
(
71-304125-XXG
)。
The 30K’s
default charging current is 2A for battery configuration.
For long run model, charger’s part number is 71-303981-03G-XXG (“xx” means the version of
charger) normally, the 60KL’s default charging current is 8A for battery configuration, and the
100KL/120KL’s default charging current is 16A for battery configuration,and the 180KL/200KL’s
default charging current is 24A for battery configuration.
8.2.3 Regulation of the system
Parameter Setting Method:
1. Connect the RS232 port of the UPS to the RS232 port of the computer with RS232 cable. Choose
the “Start>>Program>>Accessory>>Communication>>Hyper terminal” and start Hyper terminal
application. Set the COM port for “COM1” and the other setting as Figure 7.1.
Communication protocol setting
Display setting
Figure 7.1 Hyper terminal setting
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...