55
b5
Bypass mode
b4
UPS Failed
b3
EPO active
b2
Test in Progress
b1
Shutdown Active
b0
mute status (bat silence)
a0
battery test ok
12.1.2 ^C0NNN<0x0d>
This command is to adjust the positive BUS voltage, the format is:
Computer: ^C0NNN<0x0d>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Voltage adjustment step: <nnn>. n=000, 011……, 999.
For example:
Computer:
^C010BUSPV
-001
<0x0d>
UPS: (ACK
Meanings: Positive BUS voltage will decrease about 0.1%.
12. 1.3 ^C0NNN<0x0d>
This command is to adjust the negative BUS voltage, the format is:
Computer: ^C0NNN<0x0d>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Voltage adjustment step: <nnn>. n=000, 001……, 999.
For example:
Computer:
^C0001
<0x0d>
UPS: (ACK
Meanings: Negative BUS voltage will increase about 0.1%.
12. 1.4 ^C0NNN<0x0d>
This command is to adjust the positive battery voltage sampling value. You can adjust the parameter to
the sampling voltage displayed on LCD and the real battery voltage. The format is:
Computer: ^C0007<0x0d>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Voltage adjustment step: <nnn>. n=000, 001……, 999.
For example:
Computer: ^C010BATPV-001<0x0d>
UPS: (ACK
Meanings: Battery sampling voltage will decrease about 0.1%.
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...