24
21
1 Beeping / second
Line connect different
Check the R/S/T input
22
1 Beeping / second
Bypass connect different
Check R phase input
24
1 Beeping / second
Parallel load different
Check the output cable
33
1 Beeping / second
Locked in bypass after
overload 3 times in 30min
Check the loads
34
1 Beeping / second
AC Input current unbalance
Check the converter
36
1 Beeping / second
INV current unbalance
Check the inverter
38
1 Beeping / second
Battery replace
Replace the battery
3A
1 Beeping / second
Cover of the maintain switch
is open
Check the cover of the
maintain switch or 2-pin
black/black cable to the
CN12 in 16-302132--XXG for
30K~80K
3C
1 Beeping / second
Utility extremely unbalanced
There are huge gap between
L1-N and L2-N,or L2-N and
L3-N,or L1-N and L3-N
Please check input voltage.
3D
1 Beeping / second
Bypass unstable
Please check if bypass
voltage is stable.
3E
1 Beeping / second
Battery Voltage High
Check the battery number
setting
3F
1 Beeping / second
Battery Voltage Unbalance
Check the charger or Battery
fuse
41
1 Beeping / second
Bypass Loss
Check the bypass
42
1 Beeping / second
ISO over temperature
Check the ISO transformer
Note:
When the UPS alarms, the UPS is still working on the original mode.
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...