34
Line I/P FUSE
F1,F2,F3,F4,F5,F6,
Fuse
Open
60-200K BAT FUSE Section
Circuit Block
Checked components
Component Type
Failure condition
BAT I/P Fuse
F1,F2,F3,F4
Fuse
Open
18A Charger Section
Circuit Block
Checked components
Component Type
Failure condition
DC FUSE
F1,F2, F3, F4
Fuse
Open
MOSFET
Q1,Q2
MOSFET
D-S short or open
SCR
UC1,UC2
SCR
Short
D
D3,D4
D
Short
60-200K PFC Section
Circuit Block
Checked components
Component Type
Failure condition
SCR
UC1,
UC2,UC3,UC4,UC5,UC6,UC7,UC8
SCR
A-K Short or open
D
D1,D2,D3,D4
D
Short
IGBT
Q1,Q2,Q3,Q4,Q5,Q6
IGBT
C-E Short
60-200K INV Section
Circuit Block
Checked components
Component Type
Failure condition
D
D1,D2,D5,D6,D7,D8,D9,D10
D
Short
IGBT
Q1,Q2,Q3,Q4,Q5,Q6,Q7,Q8,Q9,Q10,Q11,Q12
IGBT
C-E Short
60-200K BYPASS Section
Circuit Block
Checked components
Component Type
Failure condition
SCR
SCR1,SCR2,SCR3
SCR
Short or Open
RLY
RLY10,RLY11,RLY12
RELAY
Short or Open
INV FUSE
F1,F2,F3
FUSE
Open
Note:
If the fuse is in “open” status, don’t replace the fuse only. In most of cases, open fuse is caused by
other failed components. Therefore, before restarting the UPS, you must find all failed components and
replace them.
8.2.4.4 30-200K Major parameters of Rectifier and PFC and SPS section
。
The most likely problems occur on the Rectifier and PFC section including: open fuse, broken IGBT,
broken Diode, broken SCR, and broken IGBT/SCR driver resistor. When checking PFC section, directly
check the IGBT with Resistance probe or the Diode Voltage Droop probe with multimeter.
30K PFC Section
Checked components
Instrument function
Reference
Value
Failed
condition
UC1,UC2,UC3,UC4,UC5,
UC6,UC7,UC8UC9,
UC10,UC11,UC12
(A, K)
Resistance
infinite
Short
(G, K)
Resistance
»
20Ω
Short
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...