2. Electric Specifications
CAPACITY*
30KVA/30KW
60KVA/60KW
100KVA/100KW 120KVA/120KW 180KVA/180KW 200KVA/200KW
INPUT
Voltage
Range
Low Line Loss
110 VAC(L-N) ± 3 % at 50% Load
176 VAC(L-N) ± 3 % at 100% Load
Low Line Comeback
Low Line Loss V 10V
High Line Loss
300 VAC(L-N) ± 3 %at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
Three phase with Neutral
Power Factor
≧
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC(208 will derating to 90%)
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
Battery mode
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
Current Crest Ratio
3:1 max
Harmonic Distortion
≦
2 % @ 100% Linear Load;
≦
5 % @ 100% Non-linear Load
Transfer
Time
Line
Battery
0 ms
Inverter
Bypass
0 ms
Inverter
ECO
<10 ms
EFFICIENCY
AC mode
> 95.5%
Battery Mode
> 94.5%
BATTERY
Standard
Model
Type
12 V /7 Ah
NA
Numbers
(16+16)pcs*2stri
ng
Recharge Time
7hours
Charging Current
2.0 A ± 10%
(max.)
Charging Voltage
13.65V ± 1%
Long-run
Model
Type
Depending on applications
Numbers
32 - 40
Charging Current
1.0~12.0A
±10%
(Adjustable)
1.0~18.0A
±10%
(Adjustable)
2.0~36.0A ±10% (Adjustable)
Each step 2A
3.0~54.0A ±10% (Adjustable)
Each step 3A
Charging Voltage
13.65VDC± 1%
PHYSICAL
Model
30K
30KL
60KL
100KL
120KL
180KL
200KL
Outline
Dimension, D X W X H
815 x 300 x 1000
979 x 600 x 1600
Net Weight (kg)
207
74
74.2
250
309
311
Packaging
Dimension, D X W X H
920 x 430 x 1205
1125 x 665 x 1800
Gross Weight
(kg)
225
94.5
95
278
362
364
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 65dB
@ 1 Meter
Less than 70dB
@ 1 Meter
Less than 75dB
@ 1 Meter
Less than 75dB
@ 1 Meter
Less than 75dB
@ 1 Meter
Less than 75dB
@ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
Содержание SBOL50KTIII-3
Страница 2: ...2 ...
Страница 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Страница 11: ...11 30k UPS inner picture 60K picture ...
Страница 12: ...12 60K picture 60K unit inner picture ...
Страница 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Страница 14: ...14 Right side panel Top side panel 100K 200K picture ...
Страница 38: ...38 HV30KL LV15KL Single Input Mode ...
Страница 45: ...45 This parameter setting is will be saved only when UPS shuts down normally with battery connection ...
Страница 46: ...46 10 2 Dynamic Password Description ...