background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 
 
 
 
 
 
 

BAX 3345 

 

                                                                                                                   

 
 

 

 
 
 

 

Operating Manual 

 

Wärtsilä  

JOVYTEC  P 

 

700VA 

 

3kVA

 

 

Содержание JOVYTEC P Series

Страница 1: ...BAX 3345 Operating Manual W rtsil JOVYTEC P 700VA 3kVA...

Страница 2: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 2 Index Date Name Revision 0 2014 06 20 Chr Fechteler 14 375 1 2014 10 29 Chr Fechteler 14 600 2 2017 08 14 D Busboom 17 262 3 4 5 6 7 8 9 10...

Страница 3: ...part of the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this ope...

Страница 4: ...G AND INDICATING ELEMENTS 21 7 1 LED AND FUNCTION KEYS 21 7 2 PARAMETERS 22 7 3 CONFIGURATION 22 7 4 TABLE OF THE ADJUSTABLE PARAMETERS 23 7 5 AUTOMATIC MANUAL BATTERY TEST 23 7 6 OFFLINE MODE 24 7 7...

Страница 5: ...1 TECHNICAL DATA AUTONOMY TIMES 31 13 2 VIEWS 32 13 2 1 BATTERY CABINET B10 B12 32 13 2 2 BATTERY CABINET BM1 33 13 2 3 BATTERY CABINET BM2 33 13 2 4 BATTERY CABINET BM3 33 13 3 CONNECTION 34 13 3 1 B...

Страница 6: ...discharging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the loca...

Страница 7: ...During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating voltag...

Страница 8: ...ns that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in th...

Страница 9: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Страница 10: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Страница 11: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Страница 12: ...factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms...

Страница 13: ...rsion factor 3 at linear load Overload behaviour 100 to 125 for 60 seconds 125 150 for 10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failur...

Страница 14: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 14 238 152 5 Dimensions and views 5 1 JOVYTEC P 700 P 1500...

Страница 15: ...5 Relay Card USB Interface option Connector for external Battery Load output socket Cold output socket for consumers 5 2 Rear view JOVYTEC P 700 P 1000 Electronic Stop RS232 Interface TAE Protection C...

Страница 16: ...0VA 3kVA BAX 3345 16 USB Interface option 5 3 Rear view JOVYTEC P 1500 Electronic Stop RS 232 Interface TAE Protection Circuit Fan Input Fuse Main Input Plug Relay Card Connector for external Battery...

Страница 17: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 17 225 360 5 4 JOVYTEC P 2000 P 3000...

Страница 18: ...JOVYTEC P 2000 P 3000 Fan Fan TAE Protection Circuit RS232 Interface Electronic Stop Input Fuse Mains Input Plug Electronic Stop Relay Card USB Interface option Connector for external Battery Output...

Страница 19: ...ct socket 3 Connect up the battery cabinet supplied optional for longer autonomy times via the battery connection jack 4 All connecting up work is now complete P L E A S E N O T E Only trained personn...

Страница 20: ...pressing the ON OFF button and the message Switching off soon appears in the display and then the message UPS OFF The UPS unit is now shut down Please note The device fans continue to run as long as t...

Страница 21: ...s the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER button selects the param...

Страница 22: ...lue of the UPS in VA CPU VERSION 3 12 CPU software 7 3 Configuration Use of the function display and the function keys allows diverse settings to be made on the UPS unit The formalism is as follows In...

Страница 23: ...uage selection English German French Spanish Italian German Generator mode Generator Generator mode ON OFF OFF Setting RS 232 interface COM control command Setting of RS232 interface ON OFF ON The man...

Страница 24: ...1 0 02 51Hz 7 7 1 Free running ON If the input frequency is 49 3Hz this value is within the narrow input frequency range This means that the output frequency is also 49 3Hz synchronised and the UPS u...

Страница 25: ...the bypass window has the following values Bypass lower limit 230 V x 1 0 2 230 V x 0 8 184 V bypass upper limit 230 V x 1 0 15 230 V x 1 15 264 5 V A 2 tolerance was selected for the input frequency...

Страница 26: ...cessary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the s...

Страница 27: ...UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer Th...

Страница 28: ...nic STOP functionality is to be used then the bridge should be removed on the plug and an external switch opener clamped to the rear plug Actuation of the external electronic STOP switch causes the ou...

Страница 29: ...mers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restarted There is still a voltage inside and at the terminals even after the electronic STOP f...

Страница 30: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 30...

Страница 31: ...000 120 BM3 280 x 680 x 630 80 91 9 JOVYTEC P 1500 0 10 4 JOVYTEC P 1500 6 18 2 JOVYTEC P 1500 30 BM1 152 x 238 x 420 40 58 2 JOVYTEC P 1500 40 BM2 225 x 360 x 425 50 60 4 JOVYTEC P 1500 60 BM3 280 x...

Страница 32: ...3 2 Views 13 2 1 Battery Cabinet B10 B12 Battery Cabinet Type Dimensions apporx in mm Weight without Batteries in kg A B C D E B10 470 800 1090 780 470 70 B11 470 800 1340 780 470 80 B12 910 810 1620...

Страница 33: ...BM1 BM3 see Table Battery Cabinets Cabinet Socket Cable to UPS System Battery Fuses F1 F2 BATTERIE F1 F2 Air Outlet 240V ZWISCHEN KREISSPANNUNG Plastic Feet Battery Fuses F1 F2 Battery Cable to UPS Sy...

Страница 34: ...W rtsil JOVYTEC P 700VA 3kVA BAX 3345 34 13 3 Connection 13 3 1 Battery Cabinets B10 B11 B12 Battery Fuses Battery terminals F1 F2 X1 X2 PE 1 2 3...

Страница 35: ...tery cabinets are fit up with flexible connection wires At the rear of the battery cabinets are two fuses of the battery reachable F1 positive pole F2 negative pole Battery Fuses UPS Device F1 F2 JOVY...

Страница 36: ...until the battery is charged up Restoration of mains power after total discharge of the battery At the end of the bridging time the inverter switches off automatically and the consumers are no longer...

Страница 37: ...t is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now the...

Страница 38: ..._________________________________________________________________________________ ______________________________________________________________________________________ _______________________________...