Instruction Manual StackGuard 2 System
18
10198E/3
4.2.2
Switching the installation on
Switch on the installation by setting the main switch (see Section 4.1) to the
"ON" position. The following starting sequence then runs automatically:
The display...
Means
Remarks
0.007 PLA 4
Equipment.off
The ring pipe is switched
off.
0.007 PLA 4
Stop
If so configured, the
instrument waits until the
valve limit switch is in the
“closed“ position.
If no status report is
received within 25
seconds, a prioritized
fault „Ret.val.cl“ or
„Entr.val.cl“ is shown
and the installation
switches off
(
Section 6).
0.007 PLA 4
Preheat 010
The heaters are switched
on during the stated time.
If so configured, the valves
remain closed.
0.007 PLA 4
Blower on
The blower is switched on.
0.007 PLA 4
Ret.val.op
If so configured, the return
valve is opened and the
status report of the valve
limit switch is monitored.
If no status report is
received within 25
seconds, a prioritized
fault „Ret.val.cl“ or
„Entr.val.cl“ is shown
and the installation
switches off
(
Section 6).
0.007 PLA 4
Entr.val.op
If so configured, the supply
valve is opened and the
status report of the valve
limit switch is monitored.
If no status report is
received within 25
seconds, a prioritized
fault „Ret.val.cl“ or
„Entr.val.cl“ is shown
and the installation
switches off
(
Section 6).
0.007 PLA 4
Heater on
The heaters are switched
on.
If no heater is activated,
this point is skipped.
0.007 PLA 4
Start time 010
During the starting period,
the sample flow and purge
air faults are disabled.
0.007 PLA 4
Heat time 0120
During the heating time,
the maximum heating
capacity and the low
temperature limit are not
monitored.
If no heater is switched
on, the heating time is
skipped.
Starting for normal
operation
Status displays
shown during the
starting procedure
Содержание StackGuard 2
Страница 2: ...SIGRIST PHOTOMETER AG technical details subject to change 08 2005...
Страница 6: ......
Страница 58: ...Instruction Manual StackGuard 2 System 52 10198E 3...
Страница 60: ...Instruction Manual StackGuard 2 System 54 10198E 3...
Страница 62: ...Instruction Manual StackGuard 2 System 56 10198E 3 W warning 8 warning signal 19 Z zero point reading 32...