![Siemens TC12 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/siemens/tc12/tc12_installation-commissioning-and-maintenance-handbook_374544048.webp)
TC12 Installation, Commissioning & Maintenance Handbook
666/HE/43100/000
Page 38
Issue 10
Pin
PL1
PL2
1
Output
0
Output
32
2
Output
1
Output
33
3
Output
2
Output
34
4
Output
3
Output
35
5
Output
4
Output
36
6
Output
5
Output
37
7
Output
6
Output
38
8
Output
7
Output
39
9
Output
8
Output
40
10
Output
9
Output
41
11
Output
10
Output
42
12
Output
11
Output
43
13
Output
12
Output
44
14
Output
13
Output
45
15
Output
14
Output
46
16
Output
15
Output
47
17
Output
16
Output
48
18
Output
17
Output
49
19
Output
18
Output
50
20
Output
19
Output
51
21
Output
20
Output
52
22
Output
21
Output
53
23
Output
22
Output
54
24
Output
23
Output
55
25
Output
24
Output
56
26
Output
25
Output
57
27
Output
26
Output
58
28
Output
27
Output
59
29
Output
28
Output
60
30
Output
29
Output
61
31
Output
30
Output
62
32
Output
31
Output
63
33
XVCC
XVCC
34
XVCC
XVCC
35
XVCC
XVCC
36
XVCC
XVCC
37
XGND
XGND
38
XGND
XGND
39
XGND
XGND
40
XGND
XGND
Connect pins 1 to 32 to the LEDs on the wall map, and the common pin for those
32 LEDs to XVCC current sink or XGND for current source.
Connector PL3
Connect cable 667/1/22743/000, a 50 way cable with 17 sockets, to PL2 of the
PSU PCB and to PL3 of all the Digital Output PCBs in the rack.