TC12 Installation, Commissioning & Maintenance Handbook
666/HE/43100/000
Page 107
Issue 10
3.3.3.38 Phase type for current sensor (KPT) L
KPT {sensor number: 1 - 23} = {phase type no.: 0 - 255}
Comment: To specify the lamp or phase type for a current sensor as defined in
the table below. See GLD command for further information on how
lamp faults are reported.
Monitorable lamp/phase types
Type
no.
Reported Fail
Colours
Reserved 0
Intersection Vehicle (IV)
1
R, A, G
Pelican Vehicle (PV)
2
R, A, G
Intersection Pedestrian (IP)
3
Rm, Gm
Pelican Pedestrian (PP)
4
Rm, Gm
Wait Indicator 40 Watt (W4)
5
Wt
Wait Indicator 60 Watt (W6)
6
Wt
Regulatory Sign (RS)
7
S
Switched Sign - Bulb type (SB)
8
S
Switched Sign - Tube type (ST)
9
S
Pelican Pede 60 W Wait (PPW)
10
Rm, Gm, Wt
Pelican 60 W Wait (PS)
11
R, A, G, Rm, Gm, Wt
Intersection Pede 60 W Wait (IPW)
12
Rm, Gm, Wt
Intersection Pedestrian Stream (IPS)
13
R, A, G, Rm, Gm, Wt
Reserved 14
Export Pedestrian with flashing Red (XP1)
15
Rm, Gm
Export Vehicle with flashing Green (XV1)
16
R, A, G
Export Vehicle Filter - flashing Amber Ball (XV2)
17
Fl.B
Export Vehicle - flashing Amber signal group
(XV3)
18
R, A, G, FL.A
Pelican Pede 40 W Wait (PP4)
19
Rm, Gm, Wt
Pelican 40 W Wait (PS4)
20
R, A, G, Rm, Gm, Wt
Intersection Pede 40 W (IP4)
21
Rm, Gm, Wt
Intersection 40 W Wait (IS4)
22
R, A, G, Rm, Gm, Wt
Sensor Unused - No type defined
255
3.3.3.39 Mains States Input Sense (KIS) L
KIS{0 - 3} = {00000000 - 11111111} (0)
Comment: Enables the sense of the signals used to indicate lamp mains
states to be inverted for any input line. This would be required if the
controller provided closed contacts for active Green confirm
outputs. Usage is similar to the GIS command.
3.3.3.40 Confirmation and Learn Count (KLC)
KLC={4 - 1500} (12)
Comment:
To change number of readings required to confirm a failure or
replacement, or learn a new characteristic.