TC12 Installation, Commissioning & Maintenance Handbook
666/HE/43100/000
Page 112
Issue 10
Comment: Indicates the dim/bright state for each of the controller lamp
supplies as shown below:
0 - state undefined (no change has occurred)
1 - dim
2 - bright
3.3.3.63 Display
Mains State Inputs (KDI)
KDI (input port number: 0 - 3) <enter>
Comment: Enables the state of the LMU mains state inputs to be displayed in
binary format.
The state of the input is only sampled at mains peaks so that the value displayed
indicates whether the particular mains supply is on or off (because the voltage
sensor output fluctuates depending on the point in the mains cycle, if the input was
sampled at other times e.g. the zero cross over point, the display may indicate that
the particular mains supply was off, erroneously).
3.3.3.64 Display Lamps ON/OFF State (KLM)
KLM (lamp supply: 0 - 1) <enter>
Comment: Indicates the state for each of the controller lamp supplies as
shown below:
6 - lamps off
7 - lamps on
8 - change in progress (debounce period)
3.3.3.65 Display LMU Learn Status (KLS)
KLS <enter>
Comment:
Displays the combined learn status bits for all aspects of all
configured sensors. Refer to KAS command, bits 0 to 3, for the
status bit definitions and layout. Only bits 0 to 3 are displayed, bits
4 to 7 are always 0.
3.3.3.66 Display Comms Message Log (GCT)
GCT (comms log code: 0 - 6)
Comment: Enables comms message and error counts to be displayed.
Note: To clear the comms log enter the command GCT 0 = 65535
Comms Log Code
Item
0
good
messages
1
CRC
errors
2
framing
errors
3
sync
errors
4
sync
timing
errors
5
sync
byte
corrupt
errors
6
4 second time out errors