TC12 Installation, Commissioning & Maintenance Handbook
666/HE/43100/000
Page 116
Issue 10
3.3.3.79 High Occupancy, timed zero occupancy (GHZ)
GHZ
= {time in seconds:
0-255
} (
8
)
Comment: Zero occupancy will be assumed after the pre-set time.
3.3.3.80 High Occupancy, smoothed occupancy high value (GHV)
GHV
= {percentage smoothed occupancy high level:
0-100
} (
90
)
Comment: Smoothed occupancy high value used for alarm detection.
3.3.3.81 High Occupancy, loop input allocation (GHL)
GHL
= {Hi-Occ Unit:
0-7
} = {input bit:
0-31
} (
255
)
Comment:
HIOCC loop input allocation, assigns an input bit (0-31) for each
HIOCC unit (or 255 to indicate that the unit is not configured).
3.3.3.82 High Occupancy, number of consecutive samples (GHN)
GHN
{loop no.
0 to 7
} = {
1 to 10
}. (
3
)
Comment:
The number of consecutive occupancy samples used to determine
if an alarm condition exists.
3.3.3.83 High
Occupancy,
smoothing factor (GHF)
GHF
= {Smoothing factor:
0-100
} (
2
).
Comment:
The smoothing factor used in calculating the new smoothed
occupancy. This value represents actual smoothing factors of 0 to
1, i.e. the default value of 2 represents 0.02 for calculation
purposes.
3.3.3.84 High
Occupancy,
clearance threshold (GHC)
GHC
= {clearance threshold:
0 to 100
} (
70
).
Comment:
The fixed clearance threshold is used to determine an alarm
clearance condition in the event that the smoothed occupancy
average is at an abnormal level prior to an alarm.
Remote Handset Commands
3.3.3.85 Open link to controller
XXC
{Opens Link to Controller}
Comment:
If the OTU is connected via a cable to the controller handset port,
inputting XXC <CR> opens the link. Note that there will be a delay
after initiating this command and the user should wait for about five
seconds before attempting to enter controller handset commands.
3.3.3.86 Close link to controller
XXO
{Returns Link to OTU}
Comment:
Closes controller link and returns control to the OTU.