Name
Type
Address
Default Range of Values / Meaning
Reference
Definition of the process
alarm 6
WORD
DBW020
0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. Conti status bit-coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-Nr. Conti status bit-going
Definition of the process
alarm 7
WORD
DBW022
0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. Conti status bit-coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-Nr. Conti status bit-going
S7 - FB Life bit
monitoring time
TIME
DBD024
0
0 = S7- Life bit monitor switched off
1 to n = Monitoring time [msec]
Analog output
0
Weight for zero point
(0 or 4 mA)
REAL
DBD028
0
Value output with the 0 or 4 mA
Reference for end value
(20 mA)
REAL
DBD032
0
Value output with the 20 mA.
Replacement value for
the analogue output at
OD
REAL DBD036
0 Replacement
value
which is output with an active
OD signal if the parameters are defined
respectively
Source for the analog
output
BYTE
DBB040
0
0 = Control signals-SIMATIC
1 = ext. default value through DR 17
2 = Gross
3 = Net
4 = Belt speed
5 = Flow rate 1
6 = Belt load Other definitions not allowed
7 = Actuation signal PID controller
Current range for the
analogue output
BYTE DBB041
0 Bit
0:
0: 0 .. 20mA
1: 4 .. 20mA
Bit 1 – 7 unused
RS232
0
RS232-printer baud rate
BYTE
DBB042
3
0 = 1200 Bit/sec.
1 = 2400 Bit/sec.
2 = 4800 Bit/s
3 = 9600 Bit/s
Other definitions not permitted.