![Siemens SIWAREX FTC Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/siemens/siwarex-ftc/siwarex-ftc_device-manual_1265490056.webp)
log or zero setting was not possible after this time has elapsed then the
corresponding technology message generated.
5.2.25 DR 3 - Maximum Negative Weight for Zero Setting upon Switch On
Zero setting means that an automatic zero setting is performed for the scale when
the supply voltage is switched on.
If zero setting upon switching on the supply voltage has been activated, then the
definition will limit the affect of the function. The reference point for the
effectiveness of the limitation is not the current weight, it is the weight that was
displayed by the scale without a previous zero setting. In operating modes "Belt
scale" and "Loss-in-weight scale", this function is not effective.
5.2.26 DR 3 - Maximum Positive Weight for Zero Setting upon Switch On
Zero setting means that an automatic zero setting is performed for the scale when
the supply voltage is switched on.
If zero setting upon switching on the supply voltage has been activated, then the
definition will limit the affect of the function. The reference point for the
effectiveness of the limitation is not the current weight, it is the weight that was
displayed by the scale without a previous zero setting. In operating modes "Belt
scale" and "Loss-in-weight scale", this function is not effective.
5.2.27 DR 3 - Maximum Negative Weight for Zero Setting
The current gross weight of the scale is defined as zero for zero setting.
For zero setting, the specification can be used to limit the effect of the function.
The reference point for the affect of the limitation is not the current gross weight.
It is the weight that the scale would show without a previous zero setting.
For scales in calibrating operation, the limit between the negative and positive
weight for zero setting is 4% of the maximum weighing range.
5.2.28 DR 3 - Maximum Positive Weight for Zero Setting
For zero setting, the specification can be used to limit the effect of the function.
The reference point for the effectiveness of the limitation is not the current weight,
it is the weight that was displayed by the scale without a previous zero setting.
For scales in calibrating operation, the limit between the negative and positive
weight for zero setting is 4% of the maximum weighing range.
5.2.29 DR 3 - Tare max. Weight T-
SIWAREX FTC accepts every weight value which is less than %-record of the
maximum weighing range with multi-range scales or weighing range 1 with a multi-
resolution scale.
On scales in verifiable application, the value is limited to 100% of the maximum
weighing range.
5.2.30 DR 3 – Operating Mode
This parameter can be used to select the suitable weighing program. One of these
weighing operating modes applies depending on the task description.
5-44