Table 11-21 Power supply cable recommendations
Description
Specification
Square area [mm
2
]
1.3 (AWG 16)
Max. length [m]
300 (AWG 16)
Note
Size the cable length and diameter to provide 19,2 VDC at power terminals at load current of
0,75 A
Table 11-22 Transmitter cable glands and entries
Description
Specification
Glands
● Material
– Nylon
1)
– Brass/Ni plated
– Stainless steel AISI 316/1.4404
● Cable cross section
– ∅ 8 to 17 mm (0.31" to 0.67")
– ∅ 5 to 13 mm (0.20" to 0.51")
Entries
1 x M25 (for current output/communication, chan‐
nel 1) and
2 x M20 (for supply and channels 2 to 4) or
1 x ½" NPT (for current output/communication,
channel 1) and
2 x ½" NPT (for supply and channels 2 to 4)
1)
: If operating temperature is below -20 °C (-4 °F), use Brass/Ni plated or stainless steel cable
glands.
Note
For hygienic applications (EHEDG) the cable glands and blind plugs must be made from
corrosion resistant material like nickel brass, stainless steel or plastic, the exposed threads
must be minimized when they are tightened up on the cable and they must have a seal (plastic
or rubber) under the threads where they screw into the terminal housing or enclosure.
Technical data
11.6 Construction
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
203
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...