ID
Icons
Message
Cause/Action
197
CH2 cable break
Check current output cable connection. Passive operation:
check external power supply.
198
CH2 output frequency too
low
The process value is below the parameter 'Lower range
value'. The output frequency cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
199
CH2 output frequency too
high
The process value is above the parameter 'Upper range
value'. The output frequency cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
200
CH2 pulse overflow
Pulse output has insufficient pulse separation. Increase
Amount per pulse, or reduce Pulse width, or reduce Pulses
per amount.
201
CH3 loop current in lower
saturation
The process value is so low that the loop current reaches
the lower saturation limit and cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
202
CH3 loop current in upper
saturation
The process value is so high that the loop current reaches
the upper saturation limit and cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
203
CH3 cable break
Check current output cable connection. Passive operation:
check external power supply.
204
CH3 output frequency too
low
The process value is below the parameter 'Lower range
value'. The output frequency cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
205
CH3 output frequency too
high
The process value is above the parameter 'Upper range
value'. The output frequency cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
186
Operating Instructions, 01/2019, A5E44030648-AB
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...