8.2.13
Datalogging on SensorFlash
Datalogging of process values can be activated under SensorFlash (menu item 3.7).
Data logging can be selected in different logging intervals for Process values and for advanced
logging of parameters.
Values with timestamp information is stored on the SensorFlash.
8.2.14
Process peak values on SensorFlash
Process peak values can be activated under "Peak values" (menu item 3.5).
Minimum and maximum process peak value is stored with timestamp information on the
SensorFlash, and also under menu item 3.5.
8.2.15
Simulation
Simulation is used for testing purposes, typically for checking that the readings of the control
system are correct.
The simulation can be activated in HMI (menu item 3.8) or via SIMATIC PDM.
Inputs/outputs simulation
Depending on the configuration of each input/output the following values can be simulated:
Table 8-5
Inputs/outputs simulation
HW configura‐
tion
Channel 1
Channel 2
Channel 3
Channel 4
Simulation value
Current output
●
4 to 20 mA
Relay output
●
●
0 (low) or 1 (high)
Signal input
●
●
0 (low) or 1 (high)
Signal output
● Current
● Pulse
● Frequency
● Status
●
●
●
● 0 to 25 mA
● 0 to 12.5 kHz
● 0 to 12.5 kHz
● 0 (low) or 1 (high)
Process value simulation
The following process values can be simulated:
● Mass flow
● Volume flow
● Standard Volume flow
Parameter assignment
8.2 Functions
SITRANS FC330
156
Operating Instructions, 01/2019, A5E44030648-AB
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...