ID
Icons Message
Cause/Action
79
Auto filtering
Check that the flowmeter is operated within its specifica‐
tions. Check other alarms to rule out HW malfunction.
87
Sensor startup
Unplug and reconnect the sensor cable. If the diagnostic
persists after the specified startup time, restart the device.
If the problem persists, contact Technical Support.
10.2.2
Transmitter diagnostics
ID
Icons
Message
Cause/Action
96
Mass flow above alarm
limit
Check process conditions. Adjust the parameter value 'Up‐
per alarm limit' to normal process conditions.
97
Mass flow above warning
limit
Check process conditions. Adjust the parameter value 'Up‐
per warning limit' to normal process conditions.
98
Mass flow below warning
limit
Check process conditions. Adjust parameter value 'Lower
warning limit' to normal process conditions.
99
Mass flow below alarm
limit
Check process conditions. Adjust the parameter value
'Lower alarm limit' to normal process conditions.
100
Volume flow above alarm
limit
Check process conditions. Adjust parameter value 'Upper
alarm limit' to normal process conditions.
101
Volume flow above warn‐
ing limit
Check process conditions. Adjust the parameter value 'Up‐
per warning limit' to normal process conditions.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
176
Operating Instructions, 01/2019, A5E44030648-AB
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...