The tube is defined as empty if the measured density value is lower than the value defined via
the Empty Tube Limit parameter.
Note
Process media density
Risk of unintentionally forcing flow values to zero if the difference between the empty tube limit
density value and the density of the process media is not sufficient.
● Ensure sufficient difference between the empty tube limit density value and the process
media density.
8.2.5
Process noise damping
Noise damping function
The dynamic sensitivity of the flow measurement signal to rapid changes in process flows can
be reduced by use of the process noise damping function. The function is typically used in
environment with:
● Strongly pulsating flow
● Changing pump speeds
● Large pressure variations
Process noise damping settings
Reduce interfering process noise by increasing the setting of the parameter Process Noise
Damping.
● Centrifugal pump (1: low)
● Triplex pump (2)
● Duplex pump (3)
● Simplex pump (4)
● Cam pump (5: high)
The default value is Duplex pump. The damping affects all functions and outputs of the sensor.
Centrifugal pump
(1, low)
Triplex pump (2)
Duplex pump
(3; default setting)
Simplex pump (4)
Cam pump (5, high)
Parameter assignment
8.2 Functions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
133
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...