ID
Icons
Message
Cause/Action
285
Data logging, < 30 days
remaining
Low available memory, which is full in 30 days at the latest.
Save logged data and free up memory space on the Sen‐
sorFlash. Increase the parameter value 'Logging interval.
286
Data logging, < 7 days re‐
maining
Low available memory, which is full in 7 days at the latest.
Save logged data and free up memory space on the Sen‐
sorFlash. Increase the parameter value 'Logging interval.
287
Data logging memory full Save logged data and free up memory space on the Sen‐
sorFlash.
288
Sensor frame tempera‐
ture simulated
Disable the simulation to return to normal operation.
10.3
Operation troubleshooting
10.3.1
Copying the application setup from one device to another
1. Remove the SensorFlash from the source device and insert the SensorFlash into the
destination device. The destination device disables the backup and signals an alarm.
2. Enter "Copy configuration" (menu item 1.8), select "OK" and press to execute the
copying. All application setup parameters are moved from the SensorFlash to the device.
Backup is still disabled and alarm signaled.
3. Remove the SensorFlash from the destination device and insert the original SensorFlash.
The device synchronizes the parameters to the SensorFlash. The alarm is cleared.
10.3.2
Updating the firmware
1. Download the new firmware bundle from www.siemens.com/FC330 (
)and save it to the SensorFlash. An instruction is also available at this site.
2. Access the flowmeter with access level Expert (the default PIN code is 2834).
3. Enter "Firmware update" (menu item 3.12), select the saved firmware bundle version and
press . The firmware update progress is shown on the display.
Diagnostics and troubleshooting
10.3 Operation troubleshooting
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
189
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...