ID
Icons
Message
Cause/Action
147
Totalizer 3 below alarm
limit
Check process conditions. Adjust the parameter value
'Lower alarm limit' to normal process conditions.
148
Transmitter electronics
temperature too high
Decrease the ambient temperature. If possible, reposition
the device in a different location. Inspect the device for
heat-related damages.
149
Transmitter electronics
temperature too low
Increase the ambient temperature. If possible, reposition
the device in a different location. Inspect the device for cold-
related damages.
150
Sensor signal disrupted
Turn off the power. Unplug and reconnect the sensor cable.
If the error still exists, contact your local Siemens repre‐
sentative.
151
SensorFlash parameter
backup disabled
A SensorFlash of another device has been inserted. Either
copy the settings from the SensorFlash to the device or
remove this SensorFlash and insert the original Sensor‐
Flash.
152
SensorFlash parameter
backup disabled
A SensorFlash of another device has been inserted. Either
copy the settings from the SensorFlash to the device or
remove this SensorFlash and insert the original Sensor‐
Flash.
153
CH1 loop current in lower
saturation
The process value is so low that the loop current reaches
the lower saturation limit and cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
154
CH1 loop current in upper
saturation
The process value is so high that the loop current reaches
the upper saturation limit and cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
155
CH1 loop current error
Invalid loop current deviation detected. Check current out‐
put cable connection. Passive operation: check external
power supply.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
182
Operating Instructions, 01/2019, A5E44030648-AB
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...