Three-positional Control valve configured in recipe 1
Parameter configuration:
Menu 2.5 Dosing
2.5.1 Dosing Mode = Control valve
Menu 2.5.5.6 Valve Control
2.5.5.6.1 Stage Setup Format = Relative
2.5.5.6.6 Current value to close = 0 mA
2.5.5.6.7 Current value to partially open = 10 mA
2.5.5.6.8 Current value to fully open = 20 mA
2.5.5.6.9 Amount for fully open = 35 %
2.5.5.6.10 Amount for partially open = 65 %
)&
①
Partially open valve
②
Fully open valve (35%)
③
Partially open valve (65%)
④
Fully closed valve
⑤
No flow
⑥
Partial flow
⑦
Full flow
8.2.8.3
Dosing operation
When the transmitter recipes have been configured, the active recipe is selected in parameter
2.5.3 "Active Recipe". The transmitter output changes according to the dosing operation and
controls the valve in the dosing process. The digital input can be configured to start dosing. HMI
provides dosing control via the dosing operating view, see Menu item 2.5: Dosing (Page 251).
All dosing setup and control can be performed via bus communication using SIMATIC PDM.
Dosing compensation
In static applications the flowrate is constant. Thus, the dosing compensation, if required, is
fixed. Use the fixed compensation by entering the amount in menu item 2.5.5.5.2 (Fixed
Compensation).
8.2.8.4
Fault handling
The transmitter fault handling provides monitoring of both dosing time and amount. The
configuration of the fault handling is done in Fault handling (menu item 2.5.5.6 for Recipe 1) .
Parameter assignment
8.2 Functions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
153
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...