There are two ways to have the alarms removed from the "Diagnostic log" (menu item 3.2.2).
● Manual: The alarm remains in the diagnostic list until the alarm is manually acknowledged
(ack.).
The time of the acknowledgement is shown in the Diagnostic log as long as the log is not
cleared.
● Auto: The alarm is removed from the Diagnostic log when the cause is removed (going).
8.2.11
Custom unit
Units can be defined/customized for all process values. This function can be used if the wanted
unit cannot be found in the list of units.
Custom unit is defined under each process value, and is available for mass flow, volume flow,
standard volume flow, density, fraction and medium temperature. Custom units menu is not
available in Custody transfer mode (CT).
8.2.12
SensorFlash
SensorFlash is a high-performance micro SD card (4 GB) with the ability to be updated by
inserting it in a PC. It is supplied with each sensor with the complete set of certification
documents including a calibration report. Material, pressure test, factory testing and order
conformance certificates are optional at ordering.
Further is contains parameter backup files, firmware logs, alarm history log, parameter change
log and data logging of process values and parameters.
The Siemens SensorFlash memory unit offers a permanent database with backup of all
parameter settings.
The SensorFlash supports copy and transfer of user settings from one flowmeter to another to
simplify commissioning. Only setup parameters are copied; no data are changed in the
receiving flowmeter.
Copying application setup from one device to another.
1. Remove the SensorFlash from the source device and insert the SensorFlash into the
destination device. The destination device disables the backup and signals an alarm.
2. Enter Copy configuration (menu item 1.8) and press to execute the copying. Move all the
application setup parameters from the SensorFlash to the device. Backup is still disabled
and alarm signaled.
3. Remove the SensorFlash from the destination device and insert the original SensorFlash.
The device synchronizes the parameters to the SensorFlash and the alarm is cleared.
4. If there is no SD-card inserted: Insert SD-Card with backup data. Press right key to continue.
5. Please wait.
6. Copy/restore parameterization - succeeded.
Press right key to continue.
Or:
Copy/restore parameterization - failed.
Press right key to continue.
Parameter assignment
8.2 Functions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
155
Содержание SITRANS FC330
Страница 14: ...Introduction 1 8 Notes on warranty SITRANS FC330 14 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 56: ...Installing mounting 4 3 Disassembly SITRANS FC330 56 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 126: ...Operating 7 2 Remote operation SITRANS FC330 126 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 158: ...Parameter assignment 8 2 Functions SITRANS FC330 158 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 216: ...Technical data 11 13 Pressure temperature ratings SITRANS FC330 216 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 224: ...Dimension drawings 12 7 Mounting bracket dimensions SITRANS FC330 224 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 236: ...HART communication B 1 Mode of operation HART function SITRANS FC330 236 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 274: ...Zero point adjustment SITRANS FC330 274 Operating Instructions 01 2019 A5E44030648 AB ...
Страница 280: ...Index SITRANS FC330 280 Operating Instructions 01 2019 A5E44030648 AB ...