Application planning
4.4 Installation location
SIPLUS HCS4200
28
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
Mounting position and clearance dimensions
●
The rack is mounted in the horizontal position. The Power Output Modules (POM) are
inserted vertically in the rack.
●
Maintain the minimum clearances from walls and other devices:
–
Sides 0 mm (side-by-side mounting permitted), top 100 mm, bottom 100 mm for
ventilation
Image 4-1
Clearances for installing an HCS4200
NOTICE
Damage due to overheating
•
You must comply with all the instructions regarding the installation location and
mounting position. Otherwise the device may malfunction or incur permanent damage
as a result of overheating.
•
Ensure that the permissible ambient temperature range is not exceeded (see Section
Technical specifications (Page 127)).