Configuration
8.3 Device/hardware configuration in the TIA Portal
SIPLUS HCS4200
70
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
PM4000 DI/DO parameters
Description
Range of values
Digital channel 9
…
Digital channel 16
•
Input (default)
•
Output
Output 1 Response to errors
…
Output 16 Response to errors
•
Switch off (default)
•
Hold last value
•
Switch on
Alarm on open circuit
•
No (default)
•
Yes
Note: If open-circuit monitoring is activated,
unused outputs are either to be shut down
again or assigned the state "1".
Alarm on absence of 24 V power supply
•
No (default)
•
Yes
Parameter PM4000 U/I
Description
Range of values
Type of voltage connection
•
Star (default)
•
Delta
•
None
Type of current converter
•
None (default)
•
1 A
•
5 A