Technical specifications
13.4 Technical specifications for I/O module
SIPLUS HCS4200
140
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
Connectable probes:
Temperature measuring range / for Pt 100 acc. to IEC 60751
0 ... 410 °C
Temperature measuring range / for Pt 1000 acc. to IEC 60751
0 ... 850 °C
Temperature measuring range / for thermocouple type J
0 ... 650 °C
Temperature measuring range / for thermocouple type K
0 ... 440 °C
Temperature measuring range / for thermocouple type L
0 ... 640 °C
Measuring inputs for current:
Number of inputs
4
Product function / Current detection
Yes
Current measuring range
0 ... 20 mA
Relative metering precision / relating to measured voltage
0.5 %
Type of electrical connection / at the measurement inputs for current
1 x 8-pin connector with tension spring connec-
tion
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for current / solid
1x (0.2 ... 1.5 mm²)
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for current / finely stranded / with core end processing
1x (0.25 ... 6 mm²)
•
Type of connectable conductor cross-section / at the measure-
ment inputs for current / for AWG conductors
1x (24 ... 8)
Communication:
Design of the interface
system interface
Display:
Number of status displays
2
Display version / as status display by LED
LED green = Ready, LED red = Error display
Auxiliary circuit:
Design of the power supply
Power supply via CIM
Active power consumption / maximum
1 W
Mechanical data:
Mounting position
vertical
Mounting type
Screw mounting to CIM
Type of ventilation
Forced ventilation
Vibration resistance
•
during operation / acc. to IEC 60068-2-6
10 ... 58 Hz / 0.075 mm. 58 ... 150 Hz / 1 g
•
during storage / acc. to IEC 60068-2-6
5 ... 8.5 Hz / 3.5 mm. 8.5 ... 500 Hz / 1 g
Shock resistance
•
acc. to IEC 60068-2-27
15g / 11 ms / 3 shocks / axis
•
acc. to IEC 60068-2-29
25 g / 6 ms / 1000 shocks / axis
Protection class IP
IP20
Depth
110 mm
Height
141 mm
Width
27 mm