Installation/mounting
5.5 Installing the I/O module (PM)
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
41
5.5
Installing the I/O module (PM)
The CIM is equipped with a receptacle for one I/O module.
NOTICE
The I/O module may only be inserted or removed when the power is off.
Tool
You will need a Torx T8 screwdriver.
Installing the I/O module
The procedure for installing an I/O module is described below:
Image 5-6
Installing the I/O module
1
Remove the blanking cover from the CIM receptacle.
2
Insert the I/O module into the receptacle and push it in as far as it will go.
3
Secure the module with screws
①
.