Technical specifications
13.2 Technical specifications for CIM
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
129
13.2
Technical specifications for CIM
product brand name
SIPLUS
Product designation
CIM4210 PROFINET
CIM4210 PROFIBUS
General technical data:
Equipment marking / acc. to DIN EN 81346-2
K
Number of slots
1
Type of power output / connectable
POM4220
Supply voltage:
Type of voltage / of the supply voltage
DC
Supply voltage / 1 / at DC / rated value
24 V
Relative negative tolerance / of the supply volt-
age
20 %
Relative positive tolerance / of the supply volt-
age
20 %
Active power consumption
3 W
Type of electrical connection / for supply voltage Connector 2x2-pin with tension spring connection
Type of connectable conductor cross-section
•
for supply voltage / solid
1x (0.2 ... 2.5 mm²)
•
for supply voltage / finely stranded / with core
end processing
1x (0.2 ... 2.5 mm²)
•
for AWG conductors / for supply voltage
1x (26 ... 12)
Communication:
Design of the interface
PROFINET IO
PROFIBUS DP
Protocol / is supported
•
PROFIBUS DP protocol
No
Yes
•
PROFINET IO protocol
Yes
No
Transfer rate
•
with PROFIBUS DP / maximum
-
12 Mbit/s
•
with PROFINET IO / maximum
100 Mbit/s
-
Type of electrical connection
•
of the PROFIBUS interface
-
9-pin D-Sub socket
•
of the PROFINET interface
2 x RJ45
-
Display:
Number of status displays
3
Display version / as status display by LED
LED green = ready, LED yellow = heating on/off, LED red = error
display