Technical specifications
13.4 Technical specifications for I/O module
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
137
PM4000 U/I
product brand name
SIPLUS
Product designation
I/O4000 U/I
General technical data:
Equipment marking / acc. to DIN EN 81346-2
K
Measuring inputs for current:
Product function / Current detection
Yes
Current measuring range
0 ... 5 A
Relative metering precision / relating to measured voltage
0.5 %
Operating frequency / 1 / rated value
50 Hz
Operating frequency / 2 / rated value
60 Hz
Type of electrical connection / at the measurement inputs for current
1 x 8-pin connector with tension spring connec-
tion
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for current / solid
1x (0.2 ... 1.5 mm²)
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for current / finely stranded / with core end processing
1x (0.25 ... 1.5 mm²)
•
Type of connectable conductor cross-section / at the measure-
ment inputs for current / for AWG conductors
1x (24 ... 16)
Measuring inputs for voltage:
Product function / voltage detection
Yes
Operating voltage / at AC / at 50 Hz / rated value
230 ... 480 V
Operating voltage / at AC / at 60 Hz / rated value
230 ... 480 V
Operating frequency / rated value
50 ... 60 Hz
Relative metering precision / relating to measured current
0.5 %
Type of electrical connection / at the measurement inputs for voltage Connector, 6-pin with tension spring connection
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for voltage / solid
1x (0.2 ... 10 mm²)
•
Type of connectable conductor cross-sections / at the measure-
ment inputs for voltage / finely stranded / with core end processing
1x (0.25 ... 6 mm²)
•
Type of connectable conductor cross-section / at the measure-
ment inputs for voltage / for AWG conductors
1x (24 ... 8)
Communication:
Design of the interface
system interface
Display:
Number of status displays
2
Display version / as status display by LED
LED green = Ready, LED red = Error display
Auxiliary circuit:
Design of the power supply
Power supply via CIM
Active power consumption / maximum