Communications
10.2 Acyclic data exchange
SIPLUS HCS4200
98
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
PROFINET: Definition is via an array [1…384] with one element of type "Bool".
PROFIBUS: Definition is via an array [1…192] with one element of type "Bool".
Each bit is assigned to one channel. The size of the array depends on the maximum
configuration possible for the HCS (number of POMs, number of channels per POM).
Data set 160 "Control of internal fans"
Byte Bit
Description
0
0
Control of internal fans
0: Temperature controlled internally (default)
1: All fans are switched on
1...7 0
Definition is via an element of the type "Byte".
Data set 190 "System reset by user"
Byte
Description
0
"R"
1
"
E
"
2
"S"
3
"
E
"
4
"T"
5
"!"
An array with 6 entries of the type "Char" is used here.
NOTICE
The data entered must not be modified.
The data set is acknowledged before the controller performs a reset about 2 seconds later.