Technical specifications
13.4 Technical specifications for I/O module
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
135
•
Type of connectable conductor cross-section / at the digital out-
puts / for AWG conductors
1x (24 ... 16)
Communication:
Design of the interface
system interface
Display:
Number of status displays
18
Display version / as status display by LED
LED green = Ready, LED red = Error display, 1
LED yellow per output: LED on - H status; LED
off -L status
Auxiliary circuit:
Design of the power supply
Power supply via CIM
Active power consumption / maximum
1 W
Mechanical data:
Mounting position
vertical
Mounting type
Screw mounting to CIM
Type of ventilation
Forced ventilation
Vibration resistance
•
during operation / acc. to IEC 60068-2-6
10 ... 58 Hz / 0.075 mm. 58 ... 150 Hz / 1 g
•
during storage / acc. to IEC 60068-2-6
5 ... 8.5 Hz / 3.5 mm. 8.5 ... 500 Hz / 1 g
Shock resistance
•
acc. to IEC 60068-2-27
15g / 11 ms / 3 shocks / axis
•
acc. to IEC 60068-2-29
25 g / 6 ms / 1000 shocks / axis
Protection class IP
IP20
Depth
110 mm
Height
141 mm
Width
27 mm
Electromagnetic compatibility:
EMC emitted interference
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
Conducted interference / due to burst / acc. to IEC 61000-4-4
2 kV signal cables
Conducted interference / due to surge / acc. to IEC 61000-4-5
DC supply cables: 0.5 kV balanced and unbal-
anced
Conducted interference / due to high-frequency radiation / acc. to IEC
61000-4-6
10 V (0.15 ... 80 MHz)
Field-bound parasitic coupling / acc. to IEC 61000-4-3
10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
Electrostatic discharge / acc. to IEC 61000-4-2
4 kV contact discharge / 8 kV air discharge
Overvoltage category
III