Parameterizing machine data
3.2 Parameterizing the control using machine data
HMI Advanced (IM4)
Commissioning Manual, 03/2009, 6FC5397-0DP10-3BA0
111
Example: In the diagram, the measured power is 10.5 kW.
Figure 3-6
Servo trace: Evaluation
If the utilization display is to indicate 100% for nominal data and higher values at operation
above the nominal working point, the normalization factor setting can be calculated from the
motor data or from the diagram and measurement as follows:
MA_SPIND_MAX_POWER = Maximum_of_the_measured_power / rated power_S1 * 100
MA_SPIND_MAX_POWER = 10500W / 7000W * 100 = 150
Enter the factor 150 in the machine data.
Содержание SINUMERIK
Страница 6: ...Preface Base software and HMI Advanced 6 Commissioning Manual 03 2009 6FC5397 0DP10 3BA0 ...
Страница 24: ...Introduction 1 5 Limits of data management HMI Advanced IM4 18 Commissioning Manual 03 2009 6FC5397 0DP10 3BA0 ...
Страница 96: ......
Страница 338: ...List of Abbreviations B 1 Abbreviations HMI Advanced IM4 332 Commissioning Manual 03 2009 6FC5397 0DP10 3BA0 ...
Страница 464: ...Programming 2 8 Operators Expanding the user interface 2 114 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Страница 562: ...Index Expanding the user interface Index 4 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Страница 566: ...Table of contents Online Help HE1 4 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Страница 598: ...Online Help HE1 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 36 ...
Страница 638: ...References for text generation Generating target language texts TX2 40 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Страница 672: ...Commissioning a system 1 4 BIOS settings PCU Basesoftware IM8 32 Commissioning Manual 03 2009 6FC5397 1DP10 4BA0 ...