Method 2:
Change the operating mode by AT commands. Enter therefore the following
commands:
+++
Activates the AT command interface and interrupts the data transfer.
AT^PARSTART<CR>
Activates the AT configuration
AT^PARSET=”TERMINAL”,”MODE”,”SUPERVISED” <CR>
Selects the Terminal Mode, or
AT^PARSET=”TERMINAL”,”MODE”,”
DISABLE
”<CR>
Selects the OPC Mode.
AT^PAREND<CR>
Deactivates the AT configuration and forces a restart of the SINAUT
MD720-3.
The device restarts in the selected new operating mode.