SINAUT MD720-3 in OPC Mode
SINAUT MD720-3
C79000-G8976-C211
59
5.3
Functions of the LEDs in OPC Mode
The device is equipped with 3 LEDs which indicate the status:
S
(Status)
Q
(Quality)
C
(Connect)
LED Status
Meaning
Fast lighting in sequence
Boot procedure
Synchronous slow blinking
Service mode
Slow lighting in sequence
Update
S, Q, C
combined
Synchronous fast blinking
Error
Blinks slowly
Device waiting for PIN input
Blinks fast
PIN error / SIM error
OFF
No GPRS attach
S (Status)
ON GPRS
attach
Blinks slowly
Booking into GSM network
1x intermittent blinking
Field strength not sufficient
2x intermittent blinking
Field strength sufficient
3x intermittent blinking
Field strength medium
ON permanently
Field strength high
Q (Quality)
OFF
Waiting for PIN input
OFF
No connection to MICRO SC
Blinks slowly
Trying to connect MICRO SC
ON
Connected to MICRO SC
C (Connect)
Blinks synchronously to
data stream
Data transfer
Blinks slowly:
1 time each second
Blinks fast :
4 times each second