SINAUT MD720-3 in Terminal Mode
SINAUT MD720-3
34
C79000-G8976-C211
AT\Q
Hardware Flow Control on/off
Executive command
Command:
AT\Q<n>
Response OK
Parameter: <n>:
0:
Hardware Flow Control (RTS/CTS) off
3:
Hardware Flow Control (RTS/CTS) on
Notice: -
ATX
Set CONNECT result code Format und Call monitoring
Executive command
Command:
ATX[<value>]
Response: OK
Parameter: <value>:
0 :
CONNECT result code only returned, dial tone and busy detection are both
disabled <Default>
1 :
CONNECT<text> result code only returned, dial tone and busy detection are
both disabled
2 :
same as 1
3 :
same as 1
4 :
same as 1
Notice:
The term “tone” is used in analogue telephone networks. The status “No dialtone” will
usually not appear, as soon as the device is booked into a GSM network. A Busy
message will be transmitted.
AT&C
AT&C Set circuit Data Carrier Detect (DCD) function mode
Executive command
Command:
AT&C[<value>]
Response:
OK
Parameter: <value>:
0 :
DCD line is always ON
1 :
DCD line is ON in the presence of data carrier only. <Default>
Notice:
-