Description of the blocks
4.2 Diagnostics block MMDiag
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
95
4.2.2
Acyclic reading of data record 92
An interconnection is provided between output parameter
RdDataOut
of the block MMOrptn
and input parameter
RdData
of the block MMDiag to enable the acyclic reading of DS92.
Data record 92 is read acyclically, i.e. it is only read when a
ReadData
operation is triggered
at MMOprtn or when either a trip or a warning is triggered by the device.
4.2.3
Message characteristics
MMDiag signals the following errors/faults:
●
DP/IO station fault (
Rack1Err
,
Rack2Err
)
●
Rack fault (
RackF_Act
)
●
Module fault (
ModF_Act
)
●
Connection fault (
BusFlt
)
An error generates a group error
GrpErr
in output parameter
Err_Act
.
The
Subn1_Id
and
Subn2_Id
parameters of the SUBNET function block (FB106) are linked
with the
Subn1Id
and
Subn2Id
parameters of the MMDiag block. These parameters forward
the error information of the primary and redundant master system. This information is
provided to output parameters
Rack1Err
and
Rack2Err
of the MMDiag block.
Message block MsgEvId1
Table 4- 7
Output messages MMDiag
Message block
Message No.
Block parameters
Message text
Message
class *
MsgEvId1
1
Rack1Err
$$BlockComment$$ Subnet1: @1%d@: Fault S
2
Rack2Err
$$BlockComment$$ Subnet2: @2%d@: Fault S
3
RackF_Act
$$BlockComment$$ Device
@1%d@/@5%d@/@3%d@: Failure
S
4
ModF_Act
$$BlockComment$$ Device
@1%d@/@5%d@/@3%d@: Module error
S
5
BusFlt
$$BlockComment$$ Device
@1%d@/@5%d@/@3%d@: Not reachable
S
6
ExtMsg1
**
$$BlockComment$$ External Message 1
S
7
ExtMsg2
**
$$BlockComment$$ External Message 2
S
8
ExtMsg3
**
$$BlockComment$$ External Message 3
S
* S = AS, OS process control fault
** User-definable message