![Siemens SIMOCODE pro Скачать руководство пользователя страница 93](http://html.mh-extra.com/html/siemens/simocode-pro/simocode-pro_programming-and-operating-manual_1265395093.webp)
Description of the blocks
4.1 Functions for all blocks
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
93
4.1.10.28
Forcing operating modes in the "Local" mode
Number of the
Feature2
bit: 8
Feature2 bit purpose
Specify whether forcing operating modes is possible in the "Local" mode.
The default setting is 0.
Bit = 0: In the "Local" mode, forcing operating modes is not possible.
Bit = 1: In the "Local" mode, forcing operating modes is possible.
4.1.10.29
Considering bad quality of automatic commands or external values
Number of the
Feature2
bit: 10
Feature2 bit purpose
Use this bit to consider the bad signal status (16#00 or 16#28) in the parameter for the
automatic commands or external values to move the block into the neutral position.
The default setting is 0.
Bit = 0: The bad signal status will not be considered.
Bit = 1: The bad signal status (
16#00
or
16#28
) in the automatic commands or external values
will be considered from the block. The block goes to a defined neutral position.
4.1.10.30
Separate interlock for each direction or position
Number of the
Feature2
bit: 16
Feature2 bit purpose
To enable the use of the "Separate interlock for each direction or position" function.
The default setting is 0.
Bit = 0: One interlock for each direction or position.
Bit = 1: Separate interlock for each direction or position.