Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
109
Phase 2: Hardware test result
●
If there is a fault,
HW fault basic unit is triggered.
●
If there is no fault:
–
The "GEN. FAULT" LED flashes when no main current is flowing.
–
The "GEN. FAULT" LED flickers if main current is flowing (in all three phases)
●
Contactor controls remain unchanged.
4.3.10
Trip reset
SIMOCODE can be reset with the trip reset command in the following situations:
●
The cause of the fault has been eliminated.
●
No ON control command is pending.
●
RdytoReset
is generated in the previous APL or at the MMRevDhl block
This resets the process image output PIO DP 0.6.
Reset trip
A trip can be reset as follows:
Table 4- 18 Trip reset
Operating mode Parameter
Value Meaning
Assigned PIO bits
AUTO /
MANUAL
TrpRstLi
1
Trip reset active, trip is reset. DP 0.6 = 1
AUTO /
MANUAL
TrpRstOp
1, 2
1
Trip reset active, trip is reset. DP 0.6 = 1
1
The command is reset at the end of the execution cycle of the block.
2
If the operation has been enabled in the Standard view (
OS_Perm = 1
).
4.3.11
Group fault
The output parameter for group error
GrpErr
is set when one of the errors listed below is
detected. The Standard view displays these errors as a group error in plain text.
●
General Fault (GenFlt) of the SIMOCODE
●
Module Fault
●
Rack Fault