Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
111
Auxiliary value
The block supports 10 programmable auxiliary values.
Table 4- 20 Structure of the auxiliary values ALARM_8P
Message No. Auxiliary
value
Block parameters
Meaning
1
1
SarrBatchName
Batch name
2
2
SdwStepNoLoc
Step number of batch
3
3
SdwBatchId
Identification number of the batch
4
4
ExtVa104
External value 4, user-definable
5
5
ExtVa105
External value 5, user-definable
6
6
ExtVa106
External value 6, user-definable
7
7
ExtVa107
External value 7, user-definable
8
8
ExtVa108
External value 8, user-definable
9
9
ExtVa109
External value 9, user-definable
10
10
ExtVa110
External value 10, user-definable
The
MsgStat1
,
MsgAckn1
, and
MsgErr1
parameters transfer the following information:
●
Message status
●
Message error
●
Message acknowledgment status
4.3.15
Messages via Event16Ts message block
Whenever an alarm is generated in the SIMOCODE pro device, this is passed on to the input
parameter
EventTsIn
of the APL block via the output parameter
EventTsOut
of the
Event16Ts block. These alarms are displayed in the Alarm view.
The MMOprtn block generates eight signals that are processed as messages at the
corresponding APL blocks with the use of the Event16Ts block. The following output
parameters of the MMOprtn block are interconnected with inputs
In1
to
In8
of the
Event16Ts block for this purpose:
●
Group warning
●
Group fault
●
Control System Fault (CSF)
●
Current warning high
●
Current warning low
●
Current trip high
●
Current trip low