Description of the blocks
4.3 MMOprtn block
SIMOCODE pro PCS 7 Library V9.0
130
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.3.18
Enabled operations
The operator permissions for control commands are configured in the
OS_Perm
structured
parameters. These are transferred to WinCC via the
OS_PermOut
and
OS_PermLog
parameters.
The block parameters are controlled via the FBs in CFC.
The activated parameter allows the operator to enter the desired commands.
The operator permissions control operation only in the faceplate.
Table 4- 39 MMOprtn operator permissions
OS_Perm
bit
OS_PermOut
bit
OS_PermLog
bit
Description
0
0
0
1 = Operator is permitted to change to AUTO
mode.
1
1
1
1 = Operator is permitted to change to
MANUAL mode.
3
3
3
1 = Operator is permitted to change to "Out of
service" (Oos) mode
14
14
14
1 = Operator is permitted to activate Trip reset
15
15
15
1 = Operator is permitted to activate emer-
gency start
16
16
16
1 = Operator is permitted to activate test
17
17
17
1 = Operator is permitted to change the upper
limit (AV) for "Alarm"
18
18
18
1 = Operator is permitted to change the upper
limit (AV) for "Warning"
19
19
19
1 = Operator is permitted to change the lower
limit (AV) for "Alarm"
20
20
20
1 = Operator is permitted to change the lower
limit (AV) for "Warning"
21
21
21
1 = Operator is permitted to update data